A Single-Phase DG Generation Unit With Shunt Active Power Filter Capability (Articolo in rivista)

Type
Label
  • A Single-Phase DG Generation Unit With Shunt Active Power Filter Capability (Articolo in rivista) (literal)
Anno
  • 2008-01-01T00:00:00+01:00 (literal)
Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#doi
  • 10.1109/TIE.2008.918642 (literal)
Alternative label
  • Maurizio Cirrincione, Marcello Pucci, Gianpaolo Vitale (2008)
    A Single-Phase DG Generation Unit With Shunt Active Power Filter Capability
    in IEEE transactions on industrial electronics (1982. Print)
    (literal)
Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#autori
  • Maurizio Cirrincione, Marcello Pucci, Gianpaolo Vitale (literal)
Pagina inizio
  • 2093 (literal)
Pagina fine
  • 2110 (literal)
Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#url
  • http://ieeexplore.ieee.org/search/searchresult.jsp?action=search&sortType=&rowsPerPage=25&searchField=Search_All&matchBoolean=true&queryText=((%22Authors%22:vitale%20g.)%20AND%20%22Document%20Title%22:DG) (literal)
Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#numeroVolume
  • 55 (literal)
Rivista
Note
  • ISI Web of Science (WOS) (literal)
  • Google Scholar (literal)
Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#affiliazioni
  • Université de Technologie de Belfort-Montbéliard (UTBM), Belfort, France, m.cirrincione@ieee.org , † I.S.S.I.A.-C.N.R. (Institute on Intelligent Systems for the Automation), Palermo – Italy, (literal)
Titolo
  • A Single-Phase DG Generation Unit With Shunt Active Power Filter Capability (literal)
Abstract
  • This paper deals with a single-phase distributed generation (DG) system with active power filtering (APF) capability, devised for utility current harmonic compensation. The idea is to integrate the DG unit functions with shunt APF capabilities, because the DG is connected in parallel to the grid. With the proposed approach, control of the DG unit is performed by injecting into the grid a current with the same phase and frequency of the grid voltage and with an amplitude depending on the power available from renewable sources. On the other hand, load harmonic current compensation is performed by injecting into the alternating current system harmonic currents like those of the load but with an opposite phase, thus keeping the line current almost sinusoidal. Both detection of the grid voltage fundamental and computation of the load harmonic compensation current have been performed by two neural adaptive filters with the same structure, one in a configuration “notch” and the other in the complementary configuration “band.” The “notch” filter has been used to compute the compensationg current by eliminating only the contribution of the fundamental of the load current, (literal)