http://www.cnr.it/ontology/cnr/individuo/prodotto/ID194957
Experimental analysis of a R744 het pump equipped with an ejector (Contributo in atti di convegno)
- Type
- Label
- Experimental analysis of a R744 het pump equipped with an ejector (Contributo in atti di convegno) (literal)
- Anno
- 2012-01-01T00:00:00+01:00 (literal)
- Alternative label
Silvia Minetto(a), Riccardo Brignoli(b), Krzysztof Banasiak(c), Armin Hafner(d), Francesco
Tesser (b) (2012)
Experimental analysis of a R744 het pump equipped with an ejector
in 10th IIR Gustav Lorentzen Conference on Natural Refrigerants, Delft (Olanda), 25-27 giugno 2012
(literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#autori
- Silvia Minetto(a), Riccardo Brignoli(b), Krzysztof Banasiak(c), Armin Hafner(d), Francesco
Tesser (b) (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#titoloVolume
- Proceedings of the 10th IIR Gustav Lorentzen Conference on Natural Refrigerants, Delft, The Netherlands, 2012 (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#affiliazioni
- (a) Institute for Construction Technologies, National Research Council, Corso Stati Uniti 4, 35127 Padova, Italy
(b) Dipartimento di Fisica Tecnica, University of Padova, via Venezia 1, 35131 Padova, Italy
(c) Silesian University of Technology, Institute of Thermal Technology, Konarskiego 22, Gliwice, 44-100, Poland
(d) SINTEF Energy Research, Kolbjørn Hejes v. 1D, 7465 Trondheim, Norway. (literal)
- Titolo
- Experimental analysis of a R744 het pump equipped with an ejector (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#isbn
- 978-2-913149-90-8 (literal)
- Abstract
- This paper presents the experimental analysis of a prototype R744 water/water heat pump (5 kW heating
power at 0°C evaporation temperature, 100 bar gas cooler pressure, 35°C gas cooler outlet temperature)
which was equipped with a two-phase ejector. According to the traditional lay-out, the energy that was
recovered from the expansion process inside the ejector improved the circulation of refrigerant through the
evaporator. The same heat pump was also provided with a back-pressure valve as the expansion device, i.e. a
direct comparison of the performance was possible between the heat pump systems, either equipped with the
ejector or the expansion valve.
Tests were performed to evaluate the performance when the heat pump produced hot tap water, i.e. heating
water from the main waterworks temperature to storage temperature (~60°C). Additionally, an investigation
took place to understand how the system performed when space heating was required, i.e. providing hot
water with a limited temperature lift, however at relatively high inlet temperatures.
Experiments demonstrated that the ejector is helpful to improve the heat pump performance, thus promoting
the diffusion of R744 units also for domestic space heating and air conditioning. Technological problems
related to lubricant recovery were found. (literal)