http://www.cnr.it/ontology/cnr/individuo/prodotto/ID180762
An experimental analysis of a supermarket plant working with carbon dioxide as refrigerant (Contributo in atti di convegno)
- Type
- Label
- An experimental analysis of a supermarket plant working with carbon dioxide as refrigerant (Contributo in atti di convegno) (literal)
- Anno
- 2007-01-01T00:00:00+01:00 (literal)
- Alternative label
Luca Cecchinato; Marco CorradiI; Silvia Minetto; Pierluigi Schiesaro (2007)
An experimental analysis of a supermarket plant working with carbon dioxide as refrigerant
in 22nd IIR International Congress of Refrigeration, Beijing, China, August, 21-26
(literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#autori
- Luca Cecchinato; Marco CorradiI; Silvia Minetto; Pierluigi Schiesaro (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#titoloVolume
- PROCEEDINGS- The 22nd IIR International Congress of Refrigeration (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#affiliazioni
- Dipartimento di Fisica Tecnica, Università degli Studi di Padova, via Venezia, 1,
Padova, I-35131, Italy ;
Arneg S.p.A., via Venezia, 58, Campo San Martino (PD), I-35010, Italy (literal)
- Titolo
- An experimental analysis of a supermarket plant working with carbon dioxide as refrigerant (literal)
- Http://www.cnr.it/ontology/cnr/pubblicazioni.owl#isbn
- Abstract
- This paper presents the experimental results of a commercial refrigeration plant for supermarkets
working with R744. The system was installed for testing purpose in a test area, simulating a 300 m2
supermarket. The system has a total capacity of 31 kW in medium temperature (MT - evaporation
temperature -10°C) and about 15 kW in low temperature (LT - evaporation temperature -35°C).
The swept volume of the compressors is 5.4 m3/h for MT and 5.9 m3/h for LT, the MT and the LT
circuits are completely separated. The MT unit has two single stage compressors in parallel, while
the LT unit has two compressors in parallel of two-stage internal compound type. In both LT and
MT units on the high pressure side, the heat is rejected to water. The throttling system includes a
differential valve or a step-motor electronic valve (acting as a controlled back-pressure valve) in
alternative, coupled with a liquid receiver and thermostatic electronic valves as the final stage. The
experimental tests were run, both in subcritical and transcritical conditions, using the two valves
varying the gas-cooler water inlet temperature from 15 to 35 °C. Different setting of the differential
valve spring were used. (literal)